YMvK 0.6_1kV 3G1,5 mm2 VULT
Installation cable
NEN: YMvKmb 0,6/1kV
Application:
· Power and control cable for general use in low voltage installations up to 1 kV, suitable for all applications indicated in NEN 1010
· Suitable for humid conditions
· Can be applied in unfavourable circumstances, like an increased ambient temperature, and in cable bundles
· The multicore versions are mainly used for auxiliary current cables and also for measurement and control purposes
Properties regarding fire performance:
· Flame retardant in accordance with NEN-EN 50266-2-4 (IEC 60332-3-24 cat. C)
Remarks:
· For a halogen free version of this product see HULT mbzh
· For cross-section of 35 mm² and above see VULTFLEX mb
· Use VULTO mb of VULTA mb in case of direct burial
Construction:
Conductor: plain annealed copper, round
? 6 mm²: solid (class 1)
? 10 mm²: stranded (class 2)
Insulation: cross-linked polyethylene (XLPE)
Assembly: 2 until 5 cores: cores cabled together, filled to make a round shape
? 6 cores: wrapped with polyester foil
Outer sheath: polyvinyl chloride (PVC) flame retardant (mb)
Electrical information:
Voltage rating: 0,6/1 kV
Test voltage: 3,5 kV
Core colours:
1 core: black
2 cores: brown, blue
3 cores: brown, black, grey (x-version)
brown, black, blue (variant version)
? 6 mm²: brown, blue, green-and-yellow (G-version)
4 cores: brown, black, grey, blue (x-version)
brown, black, grey, green-yellow (G-version)
brown, black, blue, green-and-yellow (variant version)
5 cores: brown, black, grey, black, blue (x-version)
brown, black, grey, blue, green-and-yellow (G-version)
Multicore: one core green-yellow, other cores black and numbered (G-version)
Standards/References:
NEN 3617
KEMA 42C-1-4
HD 604-4-D
NEN-EN 50266
IEC 60332-3
Additional data:
Minimum installation temperature: 0 °C
Maximum conductor temperature: +90 °C
(temporary overload permissible until +130 °C)
Operation temperature: min. -40 °C, max. +80 °C
Outer sheath: grey