Halogen Free FB 60 3G1,5 mm2 0,6-1 kV FE 30-E60
Halogen free installation cable with circuit integrity FE90/E30-E60
NEN: SMz1Kmbfbzh 0,6/1kV
Application:
· Specially developed for those parts of the circuit installations where 30 or 60 minutes circuit integrity is required
· Halogen free power and control cable for low voltage installations up to 1 kV, suitable for all applications indicated in NEN 1010 and NPR 2576, especially where stringent demands on fire safety apply
· Suitable for humid conditions
Properties regarding fire performance:
· Circuit integrity, in accordance with NEN-EN 50200 and NEN-EN 50362 and, in combination with all approved cable tray systems and mounting methods, in accordance with DIN 4102 part 12
· Fire Resistant, in accordance with IEC 60331
· Halogen free, in accordance with NEN-EN 50267 (IEC 60754)
· Low smoke, in accordance with NEN-EN-IEC 61034
· Flame retardant, in accordance with NEN-EN 50266-2-4 (IEC 60332-3-24 cat. C)
· Self-extinguishing in accordance with NEN-EN-IEC 60332-1
Remarks:
· For cross-section of 35 mm² and above see HULTFLEX mbzh FB 30/60
Construction:
Conductor: plain annealed copper, round
? 6 mm²: solid (class 1)
? 10 mm²: stranded (class 2)
Insulation: ceramifiable silicon rubber (XLSr)
Assembly: cores cabled together and filled to make a round shape or wrapped with polyester foil
Outer sheath: halogen free flame retardant thermoplastic (LSOH)
Electrical data:
Voltage rating: 0,6/1 kV
Test voltage: 3,5 kV
Core colours:
1 core: black
2 cores: brown, blue
3 cores: brown, black, grey (x-version)
brown, blue, green-and-yellow (G-version)
brown, black, blue (variant version)
4 cores: brown, black, grey, blue (x-version)
brown, black, grey, green-and-yellow (G-version)
brown, black, blue, green-and-yellow (variant version)
5 cores: brown, black, grey, black, blue (x-version)
brown, black, grey, blue, green-and-yellow (G-version)
Multi cores: one core green-and-yellow, other cores black, numbered (G-version)
Standards/References:
KEMA 164
NEN-EN 50200
NEN-EN 50362
DIN 4102-12
IEC 60331
NEN 2535
NEN 2575
NEN-EN-IEC 60332-1
NEN-EN 50266
IEC 60332-3
NEN-EN-IEC 61034
NEN-EN 50267
IEC 60754
Additional information:
Minimum installation temperature: -20 °C
Maximum conductor temperature: +90 °C
(temporary overload permissible until +130 °C
Operation temperature: min. -40 °C, max. +80 °C
Outer sheath: red