VO-YMvKasmb 0,6/1 kV 2x2,5+as2,5 mm²

Braided installation cable

NEN: VO-YMvKasmb 0,6/1 kV

Application:
· Power and control cable for general use in low voltage installations up to 1 kV, suitable for all applications indicated in NEN 1010
· For direct burial
· Also suited for above ground installations, where extra mechanical protection of the cable is required
· Can be applied in unfavourable conditions, like an increased ambient temperature, and in cable bundles
· The multicore versions are mainly used as auxiliary current cables and also for measurement and control purposes

Properties regarding fire performance:
· Flame retardant, in accordance with NEN-EN 50266-2-4 (IEC 60332-3-24 cat. C)

Remarks:
· For a halogen free version of this product see HULTO mbzh

Construction:
Conductor: plain annealed copper, round
                   ? 6 mm²: solid (class 1)
                   ? 10 mm²: stranded (class 2)
Insulation: cross-linked polyethylene (XLPE)
Assembly: 2 until 5 cores: cores cabled together, filled to make a round shape
                   ? 6 cores: cores cabled together, wrapped with polyester foil
Inner sheath: polyvinyl chloride (PVC)
Braiding: galvanized steel wires with a flexible earthwire of tinned copper wires underneath
Outer sheath: polyvinyl chloride (PVC) flame retardant (mb)

Electrical data:
Voltage rating: 0,6/1 kV
Test voltage: 3,5 kV

Core colours:
2 cores: brown, blue
3 cores: brown, black, grey
             brown, black, blue (variant version)
4 cores: brown, black, grey, blue
5 cores: brown, black, grey, black, blue
Multicores: black, numbered

Standards/References:
NEN 3617
KEMA 42C-1-4
HD 604-4-D
NEN-EN 50266
IEC 60332-3

Additional information:
Minimum installation temperature: 0 °C
Maximum conductor temperature: +90 °C
       (temporary overload permissible until +130 °C)
Operating temperature: min. -40 °C, max. +80 °C
Outer sheath colour: grey
Approval: KEMA-KEUR
Packaging: coils, drums